Product Data Sheet    

PT7FSL

In-floor fitting, less cover and flange; includes Hubbell HBL2162BLK duplex receptacle.
Hubbell offers a multiple service fire rated poke through fitting which can house two category 5 data jacks. This new series of fittings include a Hubbell Style Lineฎ 20 ampere duplex receptacle and two Hubbell category 5 modular jacks. The jacks mount flush to the cover for an unobtrusive appearance. Covers and flanges are available in gray and brass colors. Each fitting installs into a 3" cored hole, and may be easily removed from the floor and relocated. These units are UL Listed for floors with 1-4 hour fire rating.

Hubbell Wiring Device-Kellems Product Specifications
 Poke-Through Style  
 Type  2 Outlet Flush
 Item  Through-Floor fitting Only
 Core Hole Size  3"
 Flush Service Type  Duplex Receptacle with 2 Flush Category 5 Jacks
 Fire Rating  For use in 1, 1 1/2, 2, 3, or 4 hour rated unprotected reinforced concrete floors or in 1, 2, or 3 hour rated floors employing steel floor units and concrete topping (D900 Series design).
 Floor Thickness Range  2 1/4" to 7" (57.2 to 177.8)
 UL Installation Spacing  Minimum of 2 feet O.C. and not more than one unit per each 65 sq. ft. of floor area in each span.
 Cored Hole  3" (76.2) diameter
 Receptacle  Hubbell #HBL2162BLK black; NEMA 5-20R; 20A 125V; prewired
 Power Conductors  #12 AWG THHN stranded copper
 Power Conduit Tubes Material  3/4" EMT
 Low Voltage Conduit Tubes Material  1/2" EMT (two).
 Junction Box  13.0 cubic inches; eight 3/4" knock outs
 Outlet Box UL Listing  E31999
 Fire Resistance UL Listing  R8429
 Style  Flush

Features/Benefits
Features Benefits
• Two category 5 jacks. • Reliable voice and data services.
• Jacks mount flush. • Unobtrusive appearance.
• Low voltage conduit entrances. • Convenient cabling protection when needed.
• All brass appearance available. • Attractive economical alternative to solid brass.
• Receptacle mounts to fitting • Flange may be installed or removed without removing receptacle.
• Style Line rectangular device opening. • Either a power receptacle or a communication outlet may be used.






 

Hubbell Wiring Device-Kellems